BLUE GATE 6.2kVA UPS ONLINE Lf (BG6.2Lf)
PRICE: N1,250,000
Are you interested in this product?
Contact Sales:
08133686022, 08097039349
Email:
Description
BLUE GATE 6.2 LF is based on true online double conversion design which avoids all kinds of interference from the mains supply.
The output of the UPS is clean and stable, with low THD pure sine wave, adjustable input/output characteristics which enhances its flexibility and performance.
This product also serves critical servers, storage applications, and other networking equipment.
Features
- Sine wave pulse width modulation.
- Wide input voltage windows
- Pure sine wave output with less than 3% THD.
- Expandable backup time.
- Load and battery power meter display.
- Generator compatible!!!
Specifications
Capacity | 6KVA |
INPUT | |
Voltage Range | 170-270VAC or 85-135VAC 170-270VAC or 85-135VAC |
Frequency Range Phase | 50/60Hz±5% |
Power Factor | |
OUTPUT | |
Voltage Range Phase |
220VAC ±1% or 110VAC ± 1% |
Frequency Range |
50/60Hz 0.5% |
THD(linear load) | |
THD(non-linear load) | |
Load capability | Overload 110%-150%, 20s later go to bypass, automatically resume when load become normal |
Crest Factor | |
Short circuit protection | |
Waveform | Pure sine wave |
Transfer Time | 0ms (Between AC mode and Battery mode) 0ms (Between AC mode and Battery mode) |
Efficiency | ≥88% |
Model of Battery | |
DC Voltage | 192VDC |
Battery | |
Charge current(standard unit) | |
Charge current(long time unit) | 4.2A |
Recharge time | 90 % capacity after 8hrs charging |
Communication Interface | RS232; SNMP (optional) |
Parallel port |
|
Noise Level | < 55dB at 1m |
Temperature of the Environment | 0⁰C - 40⁰C |
Humidity of the Environment | 0% - 95%(non-condensing) |
Altitude of the Environment | <1500m> |
Storage temperature | −40⁰C - 50⁰C |
Standard unit Net/Gross weight (kg) | 68/89 |
Long time unit Net/Gross weight (kg) |
|
Dimension (W*D*H)mm | 305x650x867 |
Packing Dimension (W*D*H)mm | 550x853x1090 |